Quick Answer
Choose R290 (propane) for most new commercial refrigerators, R600a (isobutane) for small sealed units, and treat R490 as a non-standard hydrocarbon blend that needs destination-market confirmation before quoting. All three have a GWP of about 3 and zero ozone depletion potential, so environmental performance does not separate them — cooling capacity, charge limit, and market access do. Since 2025, F-gas rules in the EU and HFC phase-down rules in the US have made high-GWP refrigerants such as R134a (GWP 1,430) and R404A (GWP 3,922) effectively unsellable in new self-contained equipment.
1. The Three Refrigerants at a Glance
| Property | R290 (propane) | R600a (isobutane) | R490 (hydrocarbon blend) |
|---|---|---|---|
| Chemical type | Pure hydrocarbon C₃H₈ | Pure hydrocarbon C₄H₁₀ | Blend: mostly propane with isobutane and n-butane |
| GWP (100-year) | 3 | 3 | ≈3 (component-weighted; confirm supplier data) |
| ODP | 0 | 0 | 0 |
| ASHRAE 34 / ISO 817 safety class | A3 (low toxicity, high flammability) | A3 | A3 (expected — verify by blend) |
| Operating pressure | Moderate; wider capacity range | Lower than R290 | Close to R290 |
| Typical application | Reach-ins, display cases, freezers, condensing units | Domestic refrigerators, compact and under-counter units | R22/R502 retrofit in some markets |
| Typical charge, plug-in cabinet | 60–500 g depending on circuit design | 30–150 g | Varies; supplier-specific |
| ASHRAE standard designation | Yes (R-290) | Yes (R-600a) | No — see Section 3 |
The key takeaway: R290 and R600a are both low-GWP, natural refrigerants, but they are not interchangeable. R290 runs at higher pressure and covers a much wider capacity range, which is why it has become the default for new commercial plug-in cabinets. R600a's lower pressure and lower charge make it the standard for household and compact units.
2. What "Low GWP" Actually Changes
Global Warming Potential (GWP) measures how much heat a kilogram of refrigerant traps over 100 years relative to CO₂. Ozone Depletion Potential (ODP) measures damage to the ozone layer.
- R290, R600a and R744 (CO₂) have GWP of 3, 3 and 1 respectively and ODP of 0.
- R134a has GWP 1,430; R404A has GWP 3,922; R513A has GWP about 631.
- Regulations do not ban a refrigerant by name — they set a GWP threshold for an equipment category, which is why the same gas can be legal in one country and blocked in another.
For a buyer, this converts into three practical consequences:
- Market access. A cabinet charged with R134a or R404A may be refused at customs in regulated markets.
- Service cost. Under HFC quotas, legacy refrigerants become scarce and expensive over a cabinet's 8–12 year life.
- Design requirements. A3 refrigerants require spark-free electrical components, separation of ignition sources, and specific brazing and leak-test procedures. This is not a drop-in substitution.
3. Important: What R490 Is (and Is Not)
This is the most misunderstood item in refrigerant specification, and it matters for export documentation.
R490 is not an ASHRAE standard refrigerant designation. It is a name used in a Chinese patent (CN102453468B) for a mixed-hydrocarbon refrigerant composed of more than 89% and up to 99% propane, with 0.5–10% isobutane and 0.5–10% n-butane, developed as an energy-saving replacement for R22. Some suppliers use "R490" as a trade name for similar propane-rich hydrocarbon mixtures.
Why this matters when exporting:
- Customs and certification bodies recognise ASHRAE numbers, not trade names. A shipment declared simply as "R490" may be treated as an unspecified mixture and held for analysis.
- Safety classification must be established for the actual blend. A3 classification is likely for a propane-rich mixture, but it should be confirmed by the refrigerant supplier's safety data sheet.
- Charge limits and transport rules apply to the mixture's components, not to the name on the invoice.
- Serviceability is a concern. A non-standard blend cannot be topped up with off-the-shelf refrigerant in the destination market without knowing the exact composition.
Practical recommendation: If a supplier quotes R490, request the exact composition, the SDS, the GWP calculation, the safety classification, and confirmation that the destination market's customs authority accepts the declared designation. For new equipment, standard R290 is almost always the safer commercial choice.
4. Charge Limits: The Number That Sets Cabinet Size
Because R290 and R600a are A3 (flammable), standards cap the amount of refrigerant in a single circuit. This cap directly determines the largest cabinet one compressor circuit can serve.
| Standard / market | Limit for flammable hydrocarbon | What it means |
|---|---|---|
| IEC 60335-2-89:2019 (international, adopted in many markets) | Up to 500 g per circuit for commercial self-contained equipment, subject to leak-simulation and construction conditions | Enables ~1,000–1,500 L upright merchandisers on one circuit |
| EN 60335-2-89 (EU harmonised, residential self-contained) | 150 g | Limits domestic-style cabinets; commercial units follow the revised commercial provisions |
| UL 60335-2-89 Ed. 2 / US retail food equipment | 300 g per circuit (historically 150 g in older editions) | A cabinet built to 500 g IEC is not automatically importable into the US |
| ISO 5149 | Charge interacts with room volume and occupancy class | The end user's insurer or facility engineer may cite this at installation |
Two consequences buyers often miss:
- A supplier quoting "500 g, IEC compliant" without a separate US-market SKU has not engineered for North America.
- Air freight is stricter still. Under IATA Special Provision A103, a charged hydrocarbon unit can generally fly only below 100 g (0.1 kg) of refrigerant. Larger units ship de-gassed and are charged locally — which requires a licensed technician at destination.
Always ask: which ceiling was this platform engineered to, and which market SKU applies to my shipment?
5. Export Compliance by Market (2026 Snapshot)
Disclaimer: This is a reference summary, not legal advice. Regulations change frequently — confirm current requirements with the destination customs authority, an accredited certification body, or trade counsel before shipping.
| Market | Key rule | Practical effect on refrigerant choice |
|---|---|---|
| European Union | Regulation (EU) 2024/573 entered into force 11 March 2024 and replaced 517/2014. From 1 January 2025, self-contained refrigeration equipment containing F-gases with GWP ≥ 150 is barred from the market. Quota and labelling rules apply from 1 January 2025. An HFC import licence and F-gas Portal registration are required for pre-charged equipment. From 12 March 2025, exports of certain high-GWP stationary refrigeration equipment are restricted. From 2028, trade with parties outside the Montreal Protocol HFC rules is restricted. | R290 / R600a / R744 are the practical choices. An R134a plug-in cabinet is effectively unsellable in the EU. |
| United States | Under the AIM Act Technology Transitions Rule (88 FR 73098), new self-contained refrigerators and freezers must use refrigerant with GWP ≤ 150 (most classes) from 1 January 2025; low-temperature units use a ≤300 threshold. A reconsideration final rule issued in May 2026 amended provisions across several subsectors, including retail food refrigeration for remote condensing units and supermarkets and cold storage warehouses, so check EPA’s Technology Transitions page for the current text of the subsector that applies to you. | R290 is standard in new self-contained units. R600a in compact units. Check the 300 g US charge ceiling. |
| Japan | The Fluorocarbon Act uses weighted-average GWP caps by equipment category (e.g. commercial refrigeration around 750, cold storage lower). | Low-GWP hydrocarbons are comfortably within limits; verify category-specific cap. |
| Australia | New equipment above a high GWP threshold (around 2,500) was restricted from mid-2025; HFC phase-down is under the Montreal Protocol Kigali schedule. | Legacy HFCs are being phased out; low-GWP preferred. |
| China | Kigali Amendment obligations apply since 2021; HFCs are under quota. Hydrocarbons are not HFCs and are not quota-limited, but A3 safety and transport rules still apply. | R290/R600a encouraged; confirm food-contact and safety certification. |
| Middle East / Southeast Asia / other A5 markets | Kigali schedules apply by country group; many markets do not yet have equipment-level GWP bans. | Older HFC cabinets may still be legal today — but specify low-GWP to avoid stranded inventory as rules tighten. |
The commercial point: refrigerant choice is now a customs question, not just an engineering preference. A specification written in 2023 with R404A may be unsellable at the port in 2026.
6. How to Specify Refrigerant in an RFQ
A workable RFQ line should include:
- Refrigerant name and ASHRAE designation (e.g. "R-290, propane, CAS 74-98-6"), not a trade name alone.
- Charge weight per circuit and number of circuits.
- Safety classification (ASHRAE 34 / ISO 817) and the standard used for the charge limit.
- Destination-market certification (CE, UL/ETL, local equivalent) with the certificate number.
- Shipping condition — pre-charged or de-gassed, and who performs final charging.
- Service plan — technician qualification, brazing requirements, and spare-part availability.
- SDS and GWP declaration for customs paperwork.
7. Common Mistakes
- Assuming hydrocarbons are drop-in replacements. Compressor, capillary tube, evaporator, electrical components and charge weight are all engineered around one refrigerant. Never substitute in the field.
- Using fuel-grade propane or isobutane. Fuel-grade gas is odorised with ethyl mercaptan, which breaks down compressor oil and contaminates the system. Always specify refrigerant-grade.
- Comparing energy claims from different test conditions. A supplier claiming "20% saving from R290" is usually bundling door-glass and insulation upgrades. Ask for two test reports at the same ambient class.
- Ignoring service training. A3 equipment needs certified technicians and spark-free tooling. Include training in the contract.
- Treating "GWP 3" as a complete environmental story. Energy consumption over 10 years often dominates lifetime climate impact. Specify an efficient cabinet, not just a low-GWP gas.
FAQ
Q: Is R290 propane safe for commercial refrigerators? A: Yes, when the cabinet is designed for it. R290 is A3 (flammable), so the charge is limited, electrical components are sealed or ignition-protected, and the unit must pass leak-simulation tests. It has been used in millions of commercial cabinets worldwide.
Q: Can I replace R134a with R290 in an existing cabinet? A: No. R290 operates at different pressures and requires a different compressor, metering device, charge weight and safety construction. Field conversion of an R134a cabinet is not permitted.
Q: What is the difference between R290 and R600a? A: R290 (propane) runs at higher pressure and suits larger commercial cabinets; R600a (isobutane) runs at lower pressure and is used in small sealed units. Both have GWP 3 and A3 safety class, but they cannot be swapped.
Q: Is R490 a standard refrigerant? A: No. R490 is a name used in a Chinese patent for a propane-rich hydrocarbon blend, not an ASHRAE designation. Confirm composition, SDS, GWP and customs acceptance before using it in an export quotation.
Q: Why is R404A being phased out? A: R404A has a GWP of about 3,922 — nearly 4,000 times that of CO₂. It is being phased down under the EU F-gas Regulation and the US AIM Act, making it restricted in new equipment and increasingly expensive to service.
Q: What charge of R290 is allowed in a US commercial refrigerator? A: Under UL 60335-2-89 Ed. 2 for retail food equipment, the ceiling is generally 300 g per circuit. This differs from the 500 g permitted under IEC 60335-2-89:2019 in many other markets, so a separate US SKU is usually required.
Q: Can I air-freight a refrigerator charged with R290? A: Generally only if the charge is below 100 g per unit under IATA Special Provision A103. Larger units are shipped de-gassed and charged after installation by a qualified technician.
Q: Do low-GWP refrigerants save energy? A: R290 has favourable thermodynamic properties and can reduce compressor energy use by roughly 5–8% versus an equivalent R134a cabinet at the same test conditions. Always verify with like-for-like test reports.
References & standards cited
Specifications in this guide are traceable to the documents below. Where a rule depends on your destination market, confirm the current text with the authority or an accredited certification body before it goes into a contract.
- Regulation (EU) 2024/573 — fluorinated greenhouse gases (EUR-Lex)
- US EPA — Regulatory actions for Technology Transitions (AIM Act; 2023 rule at 88 FR 73098, reconsideration final rule May 2026)
- CN102453468B — mixed-alkane refrigerant described as R490 (Google Patents)
- IEC 60335-2-89:2019 / UL 60335-2-89 Ed. 2 — maximum charge of flammable refrigerant per circuit
- ASHRAE 34 / ISO 817 — refrigerant designation and safety classification
- ISO 5149 — refrigerating systems, safety and environmental requirements
- IATA DGR Special Provision A103 — air transport of equipment charged with hydrocarbon refrigerant
About this guide
Written by the SEEBERR application engineering team in Binzhou, Shandong. We manufacture commercial display refrigeration for supermarket and convenience chains in export markets; these guides describe how to specify equipment, not which of our models to buy. Send us your floor plan, product mix and climate conditions at info@seeberr.com and we will return a layout with case counts, door swings and ventilation gaps marked.